Item | Hazardous Location Motor |
Altitude | 1000 m.a.s.l. |
Ambient Temp. | -20°C to +40°C |
Balancing Method | 1/2 Key |
Bearing Cap | Yes |
Bolt Material | Carbon Steel |
Break-down Torque | 290% |
Cold Locked Rotor Time | 104 sec. |
Connection Cables Quantity | 6 |
Cooling | IC411 |
Design | B |
Drip Cover | Without |
Duty Cycle | Continuous |
Efficiency At 1 % | 70% |
Efficiency At 50 % | 50% |
Efficiency At 75 % | 62% |
Fan Cover Material | Steel |
Fan Material | Plastic |
Flange | Without |
Frame | 213/5T |
Frame Material | Cast Iron |
Frequency | 60 Hz |
Grounding Lugs | Single |
Hot Locked Rotor Time | 58 sec. |
Impregnation Method | Dip And Bake Polyester |
Insulation Class | Class F |
Ip Rating | IP55 |
L. R. Amps | 24.7A |
Locked Rotor Torque | 180% |
Lrc | 7.0X(Code K) |
Main Terminal Box Hole Size | 1" |
Main Terminal Box Hole Type | NPT |
Moment Of Inertia | 1.2 lbs./sq. ft. , 1.20 sq. ft.-lbs. |
Motor Enclosure Design | Totally Enclosed Fan Cooled |
Motor Shaft Rotation | Clockwise/Counter Clockwise , CW/CCW |
Mounting Type | Foot Mounted |
Nameplate Rpm | 1180 RPM |
No Load Amps | 2.08A |
No. Of Poles | 6 |
Noise Level | 55 dBA |
Output | 3 hp , 3 hp, 2.2 kW |
Output Rating | 2.2 kW , 3 hp, 2.2 kW |
Overload Protector | Without Overload Protector |
Painting | RAL 5009 202P (ISO 12944 - C4) |
Power Factor At 1 % | 89.5 |
Power Factor At 50 % | 86.5 |
Power Factor At 75 % | 88.5 |
Rated Current | 3.53A |
Rated Torque | 13.4 ft.-lbs. , 13.4 lbs.-ft. |
Rated Voltage | 575V AC |
Service Factor | 1.15 |
Shaft Locking Device | Without |
Shaft Material | Carbon Steel |
Shaft Material Grade | Grade 1040/45 |
Slip | 1.67% |
Starting Method | Direct On Line |
Synchronous Speed | 1200 RPM |
Temp. Rise | 80 K |
Terminal Block | Without |
Terminal Box | Left Position |
Tropicalized Painting | Without |
Voltage | 575V AC |
Weight | 200 lbs. |
Winding Thermal Protection | Thermostat - 2 wires 1 per phase 155°C , Thermostat-2 Wires 1 Per Phase 155°C |